🔌

Transformer Sizing Calculator

Determine the required kVA rating of a transformer based on connected loads, demand factor, and efficiency. Includes primary and secondary current calculation.

Results

Required Transformer Rating165.4 kVA
Minimum kVA (before margin)132.4 kVA
Primary Full-Load Current8.68 A
Secondary Full-Load Current230.16 A

📖What is it?

Transformer kVA rating is determined by the actual load demand divided by the power factor, then padded with a safety margin for future growth and fault headroom: kVA = (Total Load × Demand Factor) / PF × (1 + Safety Margin). Primary and secondary full-load currents: I = kVA × 1000 / (√3 × V).

🎯How to use

Enter the sum of all connected loads in kW. Set the demand factor (the ratio of simultaneous use — not all loads run at once) and the expected average power factor. Add a 25% safety margin for growth and harmonic derating.

💡Example scenario

Factory with 150 kW connected load, DF = 0.75, PF = 0.85, 25% margin. Demand = 112.5 kW. kVA = 112.5/0.85 = 132.4 kVA. With margin = 165.5 kVA → select standard 200 kVA transformer. Secondary (415 V) current = 200×1000/(1.732×415) = 278 A.

🏆Pro tip

Always round up to the next standard transformer size: 25, 50, 75, 100, 160, 200, 250, 315, 400, 500, 630, 800, 1000 kVA. Budget 5–10% derating for harmonic-heavy loads (VFDs, UPS, rectifiers). For transformers with >15% harmonic current, use a K-rated transformer.